Product Details:
Payment & Shipping Terms:
|
| After-sales Service Provided: | Free spare parts | Warranty: | 2 years |
|---|---|---|---|
| Type: | Air Source Heat Pump | Installation: | Freestanding |
| Housing Material: | powder coating metal or stainless steel metal | Model Number: | FA-03EVI(11.40KW) |
| Function: | House Heating Cooling Hot Water | ||
| High Light: | |||
| Model | heat pump | FA-03EVI | ||
| Unit function | Standard condition | Heating capacity | kw | 11.40 |
| kcal/h | 9802.00 | |||
| Hot water supply | T/h | 0.25 | ||
| Input power | kw | 2.77 | ||
| Low temperature conditions | Heating capacity | kw | 9.59 | |
| kcal/h | 8246.00 | |||
| Hot water supply | T/h | 0.18 | ||
| Input power | kw | 2.80 | ||
| Ultra-low temperature conditions | Heating capacity | kw | 5.95 | |
| kcal/h | 5116.00 | |||
| Hot water supply | T/h | 0.11 | ||
| Input power | kw | 2.70 | ||
| Standard condition heating input current | A | 4.85 | ||
| Max running current | A | 7.50 | ||
| Power | V/Ph/Hz | 380~400V/3N/50Hz | ||
| Unit Noise comprehensive index | Db(A) | 55.00 | ||
| Dimension | W | mm | 670./883 | |
| D | mm | 640./363 | ||
| H | mm | 820./1000 | ||
| Unit weight | kg | 115.00 | ||
| Running control | Water temperature control precision | ℃ | ±2℃ | |
| Ambient temperature range | ℃ | –25℃ – 43℃ | ||
| Refrigerants circulation structure | Throttle type | thermostatic expansion valve/electric expansion valve | ||
| Refrigerant | Type | R407C,R410A | ||
| Refrigerant charge | kg | 2.60 | ||
| Max working pressure | bar | 28.00 | ||
| Compressor | Type | Efficient fully enclosed type vortex. Copeland,panasonic EVI | ||
| Stall Current | A | 36.00 | ||
| Air-source side heat exchanger | Type | Finned heat exchanger | ||
| Qty | pc | 1.00 | ||
| Motor power | kw | 0.20 | ||
| Hhot water side heat exchanger | Type | tube in shell heat exchange/plate heat exchange | ||
| Water flow | m3/h | 1.98 | ||
| Water pressure down | kPa | 27.00 | ||
| Connecting pipe size | DN | 20.00 | ||
| Water side max working pressure | kPa | 1000.00 | ||
1,standard condition heating condiiton: air source side heat exchanger inlet air 20/15℃,hot water source intial temp 15℃,end heating temp 55℃.
2,Low temp heating condition: air source side heat exchanger inlet air 7/6℃,hot water side intial temp 10℃,end heating temp 55℃.
3,Ultra-low temperature heating conditions:air-source side heat exchanger inlet air -15/-17℃,hot water side intial temp 10℃,end heating temp 55℃.


\